Yinma Electric Technical Column · Xu Jianye

YB-12 Prefabricated Compact Substation Selection
China Package Substation · GB/T 17467 and IEC 62271-202

Yinma Electric Co., Ltd. is a China transformer and compact-substation manufacturer in Yueqing, Zhejiang. A YB unit is not a single transformer: it is an HV switchgear bay, a distribution transformer and an LV board in one outdoor enclosure. Engineer Xu Jianye wrote this guide from GB/T 17467-2020, GB/T 11022 and IEC 62271-202 — how to read the type code, what the type test covers, and how to specify for African 11 kV / 0.4 kV pad-mount sites.

YB□-12
Product series
12/0.4kV
HV / LV
1250kVA
Tested rating
IEC 62271
Switchgear family

Do not specify a compact substation as if it were a transformer

S11-M and SCB18 articles on this site cover a single apparatus under IEC 60076. A YB prefabricated substation is a switchgear assembly under IEC 62271-202. Mixing the two standards is the most common RFQ error we see from African industrial parks.

    System, not a tank. The nameplate kVA is the transformer inside. The type test is on the complete kiosk: HV compartment, transformer compartment, LV compartment and the enclosure. Two standard families. The kiosk follows GB/T 17467 / IEC 62271-202. The transformer inside still follows GB 1094 / IEC 60076 — that is a component file, not a substitute for the substation type-test report. Site interface. Cable entry, foundation, IP, maximum ambient and whether the HV bay is an RMU or a circuit-breaker cubicle must be written before price comparison. If omitted, the factory designs a 12 kV / 0.4 kV indoor-rated enclosure for 1 000 m / 40 °C.

What YB□-12/0.4-1250 means

Chinese HV/LV prefabricated substations are designated in GB/T 17467 《高压/低压预装式变电站》.

YB prefabricated substation (预装式变电站); the box □ is a layout placeholder (compartment arrangement, not a missing digit); 12 HV equipment voltage 12 kV (the Chinese 10 kV / African 11 kV class); 0.4 LV 0.4 kV; 1250 transformer rated power 1 250 kVA. Example on the Yinma type-test cover: YB□-12/0.4-1250. For an 11 kV African feeder, write HV rated voltage 11 kV or 12 kV equipment class in the protocol — do not assume a 10 kV transformer winding is already inside.

What you are buyingGoverning standardWhat the type test provesWhat it does not replace
Oil-immersed transformer (e.g. S11-M)GB 1094 / IEC 60076The tank, windings, oil, lossesHV RMU, LV board, kiosk IP
Dry-type transformer (e.g. SCB18)GB/T 1094.11 / IEC 60076-11Cast windings, PD, AN riseOutdoor enclosure and HV interlocking
YB compact substationGB/T 17467 / IEC 62271-202The assembled HV–transformer–LV kioskA transformer-only report for the kiosk

GB/T 11022 (IEC 62271-1) is the common specification for the HV switchgear inside the HV compartment. It is listed on Yinma’s YB□-12/0.4-1250 type-test report together with GB/T 17467-2020. If a bid only asks for “IEC 60076 compact substation”, send the evaluator back: 60076 is the transformer; 62271-202 is the package.

Three compartments — the technical core of a YB kiosk

Losses and temperature rise of the transformer still matter, but the kiosk fails in the field when HV interlocking, LV outgoing and enclosure ventilation are unspecified.

01

HV compartment

Usually a 12 kV RMU or metal-enclosed cubicle (load-break / vacuum CB / fuse combination as contracted). Interlocks, earthing switch and cable bushings are GB/T 11022 / IEC 62271-1 items. African 11 kV loops typically need a ring-main scheme written on the SLD, not a single incomer assumed by the factory.

02

Transformer compartment

Houses the 1 250 kVA unit on the tested sample. Oil-immersed or dry-type is a separate line in the protocol (fire, oil pit, indoor vs outdoor). The transformer still needs its own routine-test sheet (IEC 60076). That sheet is a component annex to the kiosk file.

03

LV compartment

ACB / MCCB incomer, feeders, metering, compensation if contracted. Rated current must match 1 250 kVA at 0.4 kV (about 1 800 A on the LV incomer — confirm on the SLD). Do not copy an LV schedule from a 630 kVA kiosk.

04

Enclosure

Outdoor metallic kiosk: IP, corrosion class, roof ventilation and door interlocking. Temperature-rise of the enclosure is a GB/T 17467 / IEC 62271-202 type-test item — distinct from transformer winding rise. Coastal or 45 °C sites need the ambient written, not the 40 °C default.

Quantities that belong on a compact-substation RFQ

These are assembly ratings. Transformer P₀ / Pₖ still appear, but they do not define the kiosk.

QuantityMeaningTypical contract value for YB□-12/0.4-1250
Ur HVRated voltage of the HV equipment12 kV equipment class; winding voltage as contracted (10 / 11 / 12 kV)
Ur LVLV rated voltage0.4 kV (0.415 kV if the African board is 415 V — write it)
SrTransformer rated power1 250 kVA on the tested sample; other kVA is a different type file
HV short-time / peakWithstand of the HV compartmentPer GB/T 11022 / IEC 62271-1 as contracted (e.g. 20 kA / 50 kA class — do not invent; copy the bid)
IP of enclosureIngress protection of the kioskMust be a number (IP33 / IP44 …). “Outdoor” is not an IP.
Enclosure temperature classIEC 62271-202 / GB/T 17467Type-test item for the assembled kiosk
Internal arc (IAC)IEC 62271-202 if specifiedOnly if the bid requires it. Yinma’s cover page does not by itself prove an IAC class — ask for the IAC pages if the tender lists AFL/AFR.
Routine vs type vs commissionedGB/T 17467 test classificationThe tested file lists factory (routine), type and commissioned tests on one cover

Do not score a compact-substation bid with a transformer type-test only. Conversely, do not skip the transformer routine-test serial inside the kiosk: the 1 250 kVA nameplate still has to match its own IEC 60076 sheet. Two files, two serials, one delivery.

China compact-substation standards GB/T 17467 vs IEC 62271-202

The kiosk type test is switchgear law, not transformer law. Put both GB and IEC numbers on the substation report.

SubjectChina standard on the Yinma coverIEC counterpart
HV/LV prefabricated substation (the kiosk)GB/T 17467-2020IEC 62271-202
Common specifications for HV switchgearGB/T 11022-2011IEC 62271-1
Transformer inside (component)GB 1094 / GB/T 10228 as applicableIEC 60076 series — annex, not the kiosk cover

Yinma’s report No. 2113345792 classifies the work as factory (routine) tests + type tests + commissioned tests on one HV/LV prefabricated substation, 80 pages. Factory tests apply to the delivered unit; type tests qualify the design; commissioned tests are extra items on the order. Acceptance: kiosk serial on the enclosure = report serial; transformer serial inside = transformer routine-test serial.

Yinma Electric YB-12/0.4-1250 HV/LV prefabricated substation type test report cover, CNAS L0116, report No.2113345792
Type-test report cover — Yinma Electric HV/LV prefabricated substation YB□-12/0.4-1250. Issuing body: State Center of Supervision Test for Electrical Safety (Zhejiang) / Zhejiang Fangyuan Electrical Equipment Testing Co., Ltd. (CNAS L0116, ILAC-MRA). Report query No. 2113345792. Test category: type test. Product name on the cover: high- and low-voltage prefabricated substation — not a transformer.
Page 1 of Yinma Electric YB-12/0.4-1250 type test report listing GB/T 17467-2020 and GB/T 11022-2011
Report page 1 — No. 2113345792, 80 pages. Manufacturer and applicant: Yinma Electric Co., Ltd., 358 Chengxi Road, Lecheng, Yueqing, Zhejiang. Produced March 2021; tests 9–18 April 2021 at Jiaxing. Basis: GB/T 17467-2020 High-voltage/low-voltage prefabricated substation; GB/T 11022-2011 Common specifications for high-voltage switchgear and controlgear. Scope: factory tests, type tests and commissioned tests, all within the standard limits. Approved 18 April 2021.

This file is the type-test package for the exact kiosk series in this article (YB□-12/0.4-1250). It does not replace an S11-M or SCB18 transformer report, and those transformer reports do not replace this one. If the bid kVA, HV scheme or LV incomer differs from 1 250 kVA / 12 kV / 0.4 kV, ask whether the type file still covers the offered arrangement.

Five parameters that actually freeze a YB design

A transformer RFQ (voltage, kVA, losses, altitude, ambient) is not enough. Add HV scheme, LV schedule and enclosure.

Network and power

HV 11 kV or 12 kV equipment class; LV 400/415 V; 50 Hz; transformer kVA from the load list + 20%–25%. 1 250 kVA is the tested sample, not a default for every site.

HV bay function

Ring RMU (two load-break + one transformer tee) vs single incomer vs CB protection. Draw it. Compact substations are most often mis-quoted because the HV compartment is left as “standard RMU”.

Transformer inside

Oil-immersed vs dry-type is a fire and oil-containment choice, not a kiosk brand. State loss sequence (S11/S13 or SCB) as a component. Attach or require the transformer routine-test serial at FAT.

LV board and enclosure

Incomer rating, number of feeders, metering, IP, corrosion class, cable entry (bottom / side), foundation outline. Ambient if not 40 °C. IAC only if the tender names AFL/AFR.

Documents

Kiosk type-test covering GB/T 17467 / IEC 62271-202 + factory tests of the delivered unit + transformer routine tests + destination CoC (SONCAP / KEBS PVoC / SANS). Do not write “IEC 60076 compact substation” as the only standard.

Where a YB kiosk belongs — and where a transformer-only buy is enough

The compact substation earns its freight when HV, transformer and LV must land as one outdoor assembly. It is the wrong product for a pole-mounted rural transformer.

SiteWhy a YB kioskSpecify in the protocol
Industrial park / factory gateOne pad, short LV runs, lockable HVRMU loop, LV feeder list, IP, ambient
Mine or quarry padRelocatable outdoor assemblyShort-circuit level, dust, IAC if the bid lists it
Urban commercial padNo separate HV roomSound, corrosion, cable basement entry
Solar / BESS MV skidFactory-assembled MV–LV interfaceInverter harmonics on LV; HV protection scheme
Rural 11 kV pole or pad transformer onlyNo HV RMU or LV board in the same boxBuy S11-M / S13-M; do not tender a YB kiosk

Voltage and kVA get you a transformer. A compact substation needs the HV scheme, the LV schedule and the enclosure IP as well. Five lines still suffice — they are just not the same five lines as S11-M or SCB18.

— Xu Jianye, Yinma Electric design engineer

Four questions that are specific to the kiosk, not the transformer

    Is 12 kV the same as 11 kV? 12 kV is the equipment class on the YB nameplate. The transformer winding and the RMU rated voltage must still be ordered for the actual 11 kV (or 10 kV) system. Do not treat “12” as proof that the winding is 11 kV.

    Can we accept an S11-M type-test instead of GB/T 17467? No. S11-M proves the transformer. The kiosk type test proves HV–transformer–LV assembly, enclosure and HV switchgear common requirements (GB/T 11022 / IEC 62271-1).

    Does the 80-page file include IAC? The cover lists factory, type and commissioned tests to GB/T 17467 and GB/T 11022. Internal-arc class (IAC) is only proven if those pages are in the pack and the bid asked for them. Request the IAC chapter if AFL/AFR is in the tender.

    How do you verify a China compact-substation factory? (1) Type-test kVA, HV/LV voltages and arrangement cover the bid. (2) Manufacturing of the kiosk, not a traded enclosure around a bought-in transformer with no assembly test. (3) SONCAP / KEBS record for package substations. (4) Protocol states GB/T 17467 / IEC 62271-202, GB/T 11022 / IEC 62271-1, HV scheme, LV incomer, IP, and the transformer standard as a component.

Author and manufacturer

Xu Jianye is a design engineer at Yinma Electric Co., Ltd., responsible for compact-substation and transformer export protocols and GB/T 17467 / IEC 62271-202 mapping. Yinma Electric is a China manufacturer of distribution transformers and HV/LV prefabricated substations in Yueqing, Zhejiang. Contract values follow the signed technical protocol; standards follow the latest in-force edition. Related transformer notes on this site (S11-M oil-immersed, SCB18 dry-type) cover the component inside the kiosk, not the kiosk itself.

Enquire with the kiosk five, not the transformer five
HV/LV voltages · kVA · HV scheme · LV schedule · IP / ambient

Yinma Electric will return a YB arrangement sketch, GB/T 17467 / IEC 62271-202 mapping and the factory test list for African 11 kV pad-mount sites.

Further Reading

Yinma Electric MNS withdrawable low-voltage switchgear lineup
Technical Guide

MNS Withdrawable LV Switchgear Selection: China LV Switchgear GB 7251.12 vs IEC 61439-2

Engineer Xu Jianye maps MNS drawer ratings, bus Icw, indoor IP30, and GB 7251.12 type tests to IEC 61439-2 — with Yinma Electric’s 2015 CNAS/CCC file for African 400/415 V rooms.

Read Article →
Yinma Electric SCB18 cast-resin dry-type transformer
Technical Guide

SCB18 Dry-Type Transformer Selection: China Cast-Resin GB/T 10228 vs IEC 60076-11

Engineer Xu Jianye maps SCB18-NX1 ratings, AN cooling, Dyn11, and GB/T 1094.11 type tests to IEC 60076-11 — with Yinma Electric’s CNAS type-test report for indoor African 11 kV substations.

Read Article →
Yinma Electric S11-M hermetically sealed oil-immersed distribution transformer
Technical Guide

S11-M Sealed Oil Transformer Selection: China Transformer GB/T 6451 vs IEC 60076

Engineer Xu Jianye maps S11-M ratings, ONAN temperature rise, Dyn11, and GB 1094 type tests to IEC 60076 — with Yinma Electric’s CNAS type-test report for African 11 kV / 33 kV buyers.

Read Article →

Need Technical Support or a Quote?

Our engineering team can answer follow-up questions about this article and provide specifications, pricing, and delivery schedules for your project.

Technical parameters