YB-12 Prefabricated Compact Substation Selection
China Package Substation · GB/T 17467 and IEC 62271-202
Yinma Electric Co., Ltd. is a China transformer and compact-substation manufacturer in Yueqing, Zhejiang. A YB unit is not a single transformer: it is an HV switchgear bay, a distribution transformer and an LV board in one outdoor enclosure. Engineer Xu Jianye wrote this guide from GB/T 17467-2020, GB/T 11022 and IEC 62271-202 — how to read the type code, what the type test covers, and how to specify for African 11 kV / 0.4 kV pad-mount sites.
Do not specify a compact substation as if it were a transformer
S11-M and SCB18 articles on this site cover a single apparatus under IEC 60076. A YB prefabricated substation is a switchgear assembly under IEC 62271-202. Mixing the two standards is the most common RFQ error we see from African industrial parks.
- System, not a tank. The nameplate kVA is the transformer inside. The type test is on the complete kiosk: HV compartment, transformer compartment, LV compartment and the enclosure. Two standard families. The kiosk follows GB/T 17467 / IEC 62271-202. The transformer inside still follows GB 1094 / IEC 60076 — that is a component file, not a substitute for the substation type-test report. Site interface. Cable entry, foundation, IP, maximum ambient and whether the HV bay is an RMU or a circuit-breaker cubicle must be written before price comparison. If omitted, the factory designs a 12 kV / 0.4 kV indoor-rated enclosure for 1 000 m / 40 °C.
What YB□-12/0.4-1250 means
Chinese HV/LV prefabricated substations are designated in GB/T 17467 《高压/低压预装式变电站》.
YB prefabricated substation (预装式变电站); the box □ is a layout placeholder (compartment arrangement, not a missing digit); 12 HV equipment voltage 12 kV (the Chinese 10 kV / African 11 kV class); 0.4 LV 0.4 kV; 1250 transformer rated power 1 250 kVA. Example on the Yinma type-test cover: YB□-12/0.4-1250. For an 11 kV African feeder, write HV rated voltage 11 kV or 12 kV equipment class in the protocol — do not assume a 10 kV transformer winding is already inside.
| What you are buying | Governing standard | What the type test proves | What it does not replace |
|---|---|---|---|
| Oil-immersed transformer (e.g. S11-M) | GB 1094 / IEC 60076 | The tank, windings, oil, losses | HV RMU, LV board, kiosk IP |
| Dry-type transformer (e.g. SCB18) | GB/T 1094.11 / IEC 60076-11 | Cast windings, PD, AN rise | Outdoor enclosure and HV interlocking |
| YB compact substation | GB/T 17467 / IEC 62271-202 | The assembled HV–transformer–LV kiosk | A transformer-only report for the kiosk |
GB/T 11022 (IEC 62271-1) is the common specification for the HV switchgear inside the HV compartment. It is listed on Yinma’s YB□-12/0.4-1250 type-test report together with GB/T 17467-2020. If a bid only asks for “IEC 60076 compact substation”, send the evaluator back: 60076 is the transformer; 62271-202 is the package.
Three compartments — the technical core of a YB kiosk
Losses and temperature rise of the transformer still matter, but the kiosk fails in the field when HV interlocking, LV outgoing and enclosure ventilation are unspecified.
HV compartment
Usually a 12 kV RMU or metal-enclosed cubicle (load-break / vacuum CB / fuse combination as contracted). Interlocks, earthing switch and cable bushings are GB/T 11022 / IEC 62271-1 items. African 11 kV loops typically need a ring-main scheme written on the SLD, not a single incomer assumed by the factory.
Transformer compartment
Houses the 1 250 kVA unit on the tested sample. Oil-immersed or dry-type is a separate line in the protocol (fire, oil pit, indoor vs outdoor). The transformer still needs its own routine-test sheet (IEC 60076). That sheet is a component annex to the kiosk file.
LV compartment
ACB / MCCB incomer, feeders, metering, compensation if contracted. Rated current must match 1 250 kVA at 0.4 kV (about 1 800 A on the LV incomer — confirm on the SLD). Do not copy an LV schedule from a 630 kVA kiosk.
Enclosure
Outdoor metallic kiosk: IP, corrosion class, roof ventilation and door interlocking. Temperature-rise of the enclosure is a GB/T 17467 / IEC 62271-202 type-test item — distinct from transformer winding rise. Coastal or 45 °C sites need the ambient written, not the 40 °C default.
Quantities that belong on a compact-substation RFQ
These are assembly ratings. Transformer P₀ / Pₖ still appear, but they do not define the kiosk.
| Quantity | Meaning | Typical contract value for YB□-12/0.4-1250 |
|---|---|---|
| Ur HV | Rated voltage of the HV equipment | 12 kV equipment class; winding voltage as contracted (10 / 11 / 12 kV) |
| Ur LV | LV rated voltage | 0.4 kV (0.415 kV if the African board is 415 V — write it) |
| Sr | Transformer rated power | 1 250 kVA on the tested sample; other kVA is a different type file |
| HV short-time / peak | Withstand of the HV compartment | Per GB/T 11022 / IEC 62271-1 as contracted (e.g. 20 kA / 50 kA class — do not invent; copy the bid) |
| IP of enclosure | Ingress protection of the kiosk | Must be a number (IP33 / IP44 …). “Outdoor” is not an IP. |
| Enclosure temperature class | IEC 62271-202 / GB/T 17467 | Type-test item for the assembled kiosk |
| Internal arc (IAC) | IEC 62271-202 if specified | Only if the bid requires it. Yinma’s cover page does not by itself prove an IAC class — ask for the IAC pages if the tender lists AFL/AFR. |
| Routine vs type vs commissioned | GB/T 17467 test classification | The tested file lists factory (routine), type and commissioned tests on one cover |
Do not score a compact-substation bid with a transformer type-test only. Conversely, do not skip the transformer routine-test serial inside the kiosk: the 1 250 kVA nameplate still has to match its own IEC 60076 sheet. Two files, two serials, one delivery.
China compact-substation standards GB/T 17467 vs IEC 62271-202
The kiosk type test is switchgear law, not transformer law. Put both GB and IEC numbers on the substation report.
| Subject | China standard on the Yinma cover | IEC counterpart |
|---|---|---|
| HV/LV prefabricated substation (the kiosk) | GB/T 17467-2020 | IEC 62271-202 |
| Common specifications for HV switchgear | GB/T 11022-2011 | IEC 62271-1 |
| Transformer inside (component) | GB 1094 / GB/T 10228 as applicable | IEC 60076 series — annex, not the kiosk cover |
Yinma’s report No. 2113345792 classifies the work as factory (routine) tests + type tests + commissioned tests on one HV/LV prefabricated substation, 80 pages. Factory tests apply to the delivered unit; type tests qualify the design; commissioned tests are extra items on the order. Acceptance: kiosk serial on the enclosure = report serial; transformer serial inside = transformer routine-test serial.


This file is the type-test package for the exact kiosk series in this article (YB□-12/0.4-1250). It does not replace an S11-M or SCB18 transformer report, and those transformer reports do not replace this one. If the bid kVA, HV scheme or LV incomer differs from 1 250 kVA / 12 kV / 0.4 kV, ask whether the type file still covers the offered arrangement.
Five parameters that actually freeze a YB design
A transformer RFQ (voltage, kVA, losses, altitude, ambient) is not enough. Add HV scheme, LV schedule and enclosure.
Network and power
HV 11 kV or 12 kV equipment class; LV 400/415 V; 50 Hz; transformer kVA from the load list + 20%–25%. 1 250 kVA is the tested sample, not a default for every site.
HV bay function
Ring RMU (two load-break + one transformer tee) vs single incomer vs CB protection. Draw it. Compact substations are most often mis-quoted because the HV compartment is left as “standard RMU”.
Transformer inside
Oil-immersed vs dry-type is a fire and oil-containment choice, not a kiosk brand. State loss sequence (S11/S13 or SCB) as a component. Attach or require the transformer routine-test serial at FAT.
LV board and enclosure
Incomer rating, number of feeders, metering, IP, corrosion class, cable entry (bottom / side), foundation outline. Ambient if not 40 °C. IAC only if the tender names AFL/AFR.
Documents
Kiosk type-test covering GB/T 17467 / IEC 62271-202 + factory tests of the delivered unit + transformer routine tests + destination CoC (SONCAP / KEBS PVoC / SANS). Do not write “IEC 60076 compact substation” as the only standard.
Where a YB kiosk belongs — and where a transformer-only buy is enough
The compact substation earns its freight when HV, transformer and LV must land as one outdoor assembly. It is the wrong product for a pole-mounted rural transformer.
| Site | Why a YB kiosk | Specify in the protocol |
|---|---|---|
| Industrial park / factory gate | One pad, short LV runs, lockable HV | RMU loop, LV feeder list, IP, ambient |
| Mine or quarry pad | Relocatable outdoor assembly | Short-circuit level, dust, IAC if the bid lists it |
| Urban commercial pad | No separate HV room | Sound, corrosion, cable basement entry |
| Solar / BESS MV skid | Factory-assembled MV–LV interface | Inverter harmonics on LV; HV protection scheme |
| Rural 11 kV pole or pad transformer only | No HV RMU or LV board in the same box | Buy S11-M / S13-M; do not tender a YB kiosk |
Voltage and kVA get you a transformer. A compact substation needs the HV scheme, the LV schedule and the enclosure IP as well. Five lines still suffice — they are just not the same five lines as S11-M or SCB18.
Four questions that are specific to the kiosk, not the transformer
- Is 12 kV the same as 11 kV? 12 kV is the equipment class on the YB nameplate. The transformer winding and the RMU rated voltage must still be ordered for the actual 11 kV (or 10 kV) system. Do not treat “12” as proof that the winding is 11 kV.
Can we accept an S11-M type-test instead of GB/T 17467? No. S11-M proves the transformer. The kiosk type test proves HV–transformer–LV assembly, enclosure and HV switchgear common requirements (GB/T 11022 / IEC 62271-1).
Does the 80-page file include IAC? The cover lists factory, type and commissioned tests to GB/T 17467 and GB/T 11022. Internal-arc class (IAC) is only proven if those pages are in the pack and the bid asked for them. Request the IAC chapter if AFL/AFR is in the tender.
How do you verify a China compact-substation factory? (1) Type-test kVA, HV/LV voltages and arrangement cover the bid. (2) Manufacturing of the kiosk, not a traded enclosure around a bought-in transformer with no assembly test. (3) SONCAP / KEBS record for package substations. (4) Protocol states GB/T 17467 / IEC 62271-202, GB/T 11022 / IEC 62271-1, HV scheme, LV incomer, IP, and the transformer standard as a component.
Enquire with the kiosk five, not the transformer five
HV/LV voltages · kVA · HV scheme · LV schedule · IP / ambient
Yinma Electric will return a YB arrangement sketch, GB/T 17467 / IEC 62271-202 mapping and the factory test list for African 11 kV pad-mount sites.