SCB18 Cast-Resin Dry-Type Transformer Selection
China Dry-Type Transformer · GB/T 10228, GB/T 1094.11 and IEC 60076-11
Yinma Electric Co., Ltd. is a China transformer manufacturer in Yueqing, Zhejiang, supplying SCB-series cast-resin dry-type transformers for indoor African 11 kV / 33 kV substations. Engineer Xu Jianye wrote this guide from GB/T 1094.11, GB/T 10228, GB 20052 and IEC 60076-11 — ratings, losses, type tests and how to specify.
Three items to lock before buying a China dry-type transformer
Indoor dry-type units fail tenders when the loss sequence, IEC 60076-11 environmental class and enclosure IP are left blank.
- Rating code. SCB10 / SCB12 / SCB14 / SCB18 are loss sequences in GB/T 10228 — not brand names. The suffix NX1 on a nameplate is GB 20052 energy-efficiency Grade 1. Standard. A China dry-type transformer is type-tested to GB/T 1094.11; African indoor specs quote IEC 60076-11. Mapping is below. Installation. Indoor vs outdoor, AN or AF cooling, IP20–IP54 enclosure, and climatic class (C1/C2) must be written into the protocol. If omitted, the factory designs for indoor AN, IP20, 1 000 m / 40 °C.
What SCB18-2000/10-NX1 means
Cast-resin dry-type codes in China are defined in GB/T 10228 《干式电力变压器技术参数和要求》.
S three-phase; C epoxy-resin cast (solid insulation); B foil LV winding; 18 loss sequence 18 (a higher number means a lower no-load and load-loss cap); 2000/10 2 000 kVA, HV 10 kV; NX1 GB 20052 Grade 1 energy efficiency. For an 11 kV African indoor feeder, specify rated voltage 11 kV (or 10.5/11 kV). Do not stretch a 10 kV nameplate with taps.
| Sequence | Standard | Relative no-load loss | Where it is used |
|---|---|---|---|
| SCB10 | GB/T 10228 sequence 10 | Baseline of earlier Chinese dry-type stock | Older indoor plant; Africa spare-parts enquiries |
| SCB12 / SCB14 | GB/T 10228 sequences 12 / 14 | Lower than SCB10 | Common export indoor substations |
| SCB18 | GB/T 10228 sequence 18 | Lower than SCB14 (check the table for the kVA) | Current high-efficiency indoor units |
| SCB18-NX1 | GB 20052-2020 Grade 1 | Meets China Grade 1 EE limits at that kVA | Tenders that quote GB 20052 or equivalent IEC efficiency |
GB 20052-2020 sets energy-efficiency grades for both oil-immersed and dry-type distribution transformers in China. NX1 on the tested sample SCB18-2000/10-NX1 means the unit was assessed against Grade 1 limits, not a marketing suffix. African indoor specs that quote IEC 60076-11 still need the loss table (P₀, Pₖ) written as numbers — do not assume “SCB18” is understood outside China.
Core, resin-cast windings, AN cooling, enclosure
These four items set losses, temperature rise, fire behaviour and short-circuit withstand.
Core
CRGO, typically 45° mitred joints. No-load loss P₀ and no-load current I₀% are the stacking check on the routine-test report (GB/T 1094.1 / IEC 60076-1).
Cast windings
HV windings vacuum-cast in epoxy; LV usually copper foil (the “B” in SCB). Casting quality governs partial discharge and moisture ingress. African 11 kV/0.4 kV indoor units are normally Dyn11, 50 Hz.
Insulation · AN / AF
Typical thermal class F (155 °C). Winding temperature-rise limits follow GB/T 1094.11 / IEC 60076-11 for the declared class. Cooling is air-natural AN; fans (AF) are a contract option for cyclic overload, not a substitute for kVA.
Enclosure & classes
Indoor default IP20. Coastal or dusty plant rooms need a stated IP and IEC 60076-11 climatic / environmental / fire classes (commonly C2, E2, F1). These letters must appear in the protocol; they are not implied by “dry type”.
Quantities that must match the routine-test report
Check against GB/T 10228 for the declared sequence and the GB/T 1094.1 / IEC 60076-1 routine-test list.
| Quantity | Meaning | Typical limit / contract value |
|---|---|---|
| P₀ no-load loss | Iron loss, continuous | GB/T 10228 table for the SCB sequence and kVA |
| Pₖ load loss | Copper + stray, ∝ I², referred to the rated winding temperature | Same table; indoor plant with low night load is still dominated by P₀ |
| I₀% | Magnetising current / rated current | GB/T 10228 limit |
| Uₖ% | Short-circuit impedance | 10 kV class mid-kVA typically ~6%; confirm from GB/T 10228 for the exact kVA |
| Insulation level | LI / AC | 12 kV equipment: typically LI 75 kV / AC 35 kV — as contracted |
| Partial discharge | GB/T 1094.11 / IEC 60076-11 | Routine or type item as contracted; cast-resin quality check |
| Sound level | GB/T 1094.10 / IEC 60076-10 | Indoor commercial rooms: write a dB(A) cap, do not leave “standard” |
| Short-circuit | GB/T 1094.5 / IEC 60076-5 | Special test; duration commonly 2 s if specified |
Parallel operation still needs identical vector group, capacity ratio not more than 3:1, and Uₖ preferably within ±10%. Mixing an oil-immersed outdoor unit with an indoor dry-type on the same LV bus is a protection-coordination problem, not a “loss sequence” problem — write the SLD before the RFQ.
China dry-type transformer standards GB vs IEC 60076-11
Factory tests follow GB/T 1094.11 and GB/T 10228; African indoor bid evaluation follows IEC 60076-11. Put both numbers on the same report.
| Subject | China dry-type standard | IEC |
|---|---|---|
| General, ratings, test classification | GB/T 1094.1 | IEC 60076-1 |
| Insulation and external clearances | GB/T 1094.3 | IEC 60076-3 |
| Short-circuit withstand | GB/T 1094.5 | IEC 60076-5 |
| Sound levels | GB/T 1094.10 | IEC 60076-10 |
| Dry-type transformers | GB/T 1094.11 | IEC 60076-11 |
| Loss and parameter tables | GB/T 10228 | No IEC twin; quote P₀ / Pₖ numbers |
| Energy-efficiency grades | GB 20052-2020 | National EE rules differ by country |
Routine tests (every unit): winding resistance, voltage ratio and vector group, no-load, load and impedance, applied voltage, induced voltage, and partial discharge where contracted. Type tests: temperature rise, lightning impulse, and others listed on the cover. Special tests: short-circuit withstand, sound, as contracted. Acceptance: report serial = nameplate serial; the type-test file must cover the bid kVA, insulation level and thermal class.


This file is the type-test package for the exact series discussed in this article (SCB18-2000/10-NX1). It documents how a China dry-type transformer factory records GB/T 1094.11, GB/T 10228 and GB 20052 on one cover, including short-circuit (GB/T 1094.5) and sound (GB/T 1094.10). Ask for a type-test report that covers the kVA, insulation level and NX grade in your bid; do not accept a smaller-kVA or oil-immersed report as a substitute.
Five parameters fix a China dry-type transformer design
Write these five lines into the RFQ and the factory can lock kVA, loss sequence, enclosure and the test list.
Voltage and rating
HV 11/15/33 kV, LV 400/415 V, 50 Hz, Dyn11 unless the LV board says otherwise. S = P / cosφ, then 20%–25% growth margin. Indoor rooms with poor ventilation need a stated maximum ambient, not the 40 °C default.
Loss sequence and NX grade
Quote P₀ and Pₖ from GB/T 10228 for the chosen SCB sequence, or require NX1 / Grade 1 if the tender cites GB 20052. “High efficiency” without numbers is not a specification.
AN / AF and IP
AN for continuous indoor load within nameplate kVA. AF only if cyclic overload is calculated. Coastal or cement-plant rooms: state IP and C2/E2/F1 classes per IEC 60076-11.
Sound and fire
Hospitals, malls and high-rise plant rooms: write a sound-level cap (GB/T 1094.10 / IEC 60076-10) and fire class F1 if the building code requires it. Dry-type is not automatically F1.
Documents
Routine tests + type tests covering the bid type + certificate of conformity + destination-country CoC (SONCAP / KEBS PVoC / SANS). Write GB/T 1094.11 / IEC 60076-11. Do not write “factory standard”.
When a dry-type belongs on the RFQ — and when it does not
Cast-resin indoor units solve fire and oil-containment rules. They do not replace outdoor oil-immersed pole or pad units on rural feeders.
| Typical indoor use | Why dry-type | Specify in the protocol |
|---|---|---|
| Mall, hospital, high-rise, data hall | No oil pit; fire compartment rules | Sound dB(A), F1 if required, IP, max ambient |
| Industrial plant room next to process | Indoor step-down beside LV boards | Harmonics / K-factor if VFD heavy; AN or AF |
| Coastal city indoor substation | Resin vs oil leak in a basement | C2/E2, enclosure IP, anti-corrosion hardware |
| Rural 11 kV pole / pad outdoor | Not the dry-type use case | Specify oil-immersed S11-M / S13-M instead |
Voltage, kVA, P₀/Pₖ or NX grade, IP plus C2/E2/F1, maximum ambient — five lines are enough for a China dry-type transformer factory to freeze the winding, enclosure and test plan.
Four technical questions at bid stage
- Is SCB18 a China-only code? Yes. Write the GB/T 10228 P₀ and Pₖ values (and NX1 if Grade 1 is required) so an IEC 60076-11 evaluator can score the bid without knowing the SCB letters.
Can a GB/T 1094.11 report be used under IEC 60076-11? The parts listed on Yinma’s SCB18-2000/10-NX1 cover map to IEC 60076-1/-3/-5/-10/-11. Require both numbers on the same report.
Does dry-type remove the need for fire protection? No. IEC 60076-11 fire class F1 is a declared option. State it if the building code needs it.
How do you verify a China dry-type transformer factory? (1) Type-test kVA, insulation and NX grade cover the bid. (2) Manufacturing, not trading only. (3) SONCAP / KEBS handling record. (4) Protocol states GB/T 1094.11 / IEC 60076-11, Uₖ, Dyn11, AN/AF, IP and C2/E2/F1.
Enquire with five parameters
Voltage · kVA · P₀/Pₖ or NX grade · IP / C2 E2 F1 · maximum ambient
Yinma Electric will return SCB-sequence advice, GB/IEC mapping and the factory test list for indoor African 11 kV / 33 kV substations.