MNS Withdrawable LV Switchgear Selection
China LV Switchgear · GB 7251.12 and IEC 61439-2
Yinma Electric Co., Ltd. is a China manufacturer of transformers and low-voltage assemblies in Yueqing, Zhejiang. An MNS board is not a transformer and not a compact-substation kiosk: it is a withdrawable power switchgear assembly (PSC) under GB 7251.12 / IEC 61439-2. Engineer Xu Jianye wrote this guide from the 2015 CNAS safety type-test file — ratings, indoor IP, temperature-rise conditions, and how to specify for African 400/415 V rooms.
Do not specify an LV board as if it were a transformer or a YB kiosk
S11-M and SCB18 on this site are IEC 60076 apparatus. YB-12 is an IEC 62271-202 outdoor assembly. MNS is an indoor low-voltage PSC under IEC 61439-2. A kVA nameplate does not define this product.
- Assembly, not a winding. The type test is on the complete board: enclosure, main bus, distribution bus, withdrawable functional units and the incoming device. Two document families. The board follows GB 7251.12 / IEC 61439-2. Breakers, contactors and meters inside still have their own component certificates — those sheets do not replace the assembly type-test. Room interface. Incoming current, short-circuit Icw, form of separation, IP, indoor vs outdoor, and whether drawers or fixed feeders are required must be written before price comparison. If omitted, a Chinese indoor MNS is quoted at Ue 380 V, IP30, 1 000 m / 40 °C.
What “MNS” means on a Chinese LV RFQ
MNS is a withdrawable low-voltage complete switchgear layout used in GB 7251.12 《低压成套开关设备和控制设备 第2部分:成套电力开关和控制设备》.
On Yinma’s file the product name is 抽出式低压成套开关柜 (withdrawable LV complete switchgear) and the type is MNS. It is a PSC assembly: functional units withdraw on drawers, the bus is rear or top, the incomer is usually an ACB. It is not GGD (fixed panel), not GCS (another Chinese withdrawable family), and not the LV compartment of a YB kiosk — that compartment is a component of IEC 62271-202, not a substitute for an IEC 61439-2 board type-test.
| What you are buying | Governing standard | What the type test proves | What it does not replace |
|---|---|---|---|
| Oil or dry transformer | GB 1094 / IEC 60076 | Tank or cast windings, losses | Busbar Icw, drawers, LV IP |
| YB compact substation | GB/T 17467 / IEC 62271-202 | Outdoor HV–transformer–LV kiosk | A full indoor LV room board |
| MNS withdrawable LV board | GB 7251.12 / IEC 61439-2 | Indoor PSC assembly, bus, IP | A transformer or kiosk report |
African tenders still write “IEC 60439 LV panel”. IEC 60439 was withdrawn. The in-force counterpart of GB 7251.12-2013 is IEC 61439-2 (power switchgear and controlgear assemblies), with IEC 61439-1 as the general rules. If the bid only cites 60439, map it in the protocol; do not leave the edition blank.
What actually distinguishes an MNS board
Rated voltage is the easy line. The board fails in the field when Icw, drawer scheme, temperature-rise ventilation and IP are left as “standard MNS”.
Withdrawable units
Feeders and motor starters sit in drawers that isolate from the bus for maintenance. Draw count, module height and whether the ACB is withdrawable must appear on the SLD. A GGD-style fixed door is a different product — do not mix the two on one line item.
Main and distribution bus
Yinma’s tested sample: main bus InA 4 000 A, Icw 80 kA; distribution bus Inc 1 000 A, Icw 50 kA. The CCC family listing also prints a wider main-bus window (see the certificate caption). Quote the bus you will actually install, not the highest number on any page.
Indoor enclosure
The file is 户内型, IP30. That is a dry LV room, not an outdoor pad. Coastal or dusty African rooms often need IP42 / IP54 and a corrosion class — write them; IP30 will not appear by magic.
Temperature-rise set-up
The 2015 report notes that during the temperature-rise test ten 65 W fans were running. If the site has no forced ventilation, that test does not prove an unventilated column. State natural vs forced cooling in the protocol.
Quantities that belong on an MNS RFQ
These are assembly ratings. Transformer kVA only sizes the incomer; it does not define the board.
| Quantity | Meaning | On Yinma’s tested MNS sample |
|---|---|---|
| Ue | Rated operational voltage | 380 V (write 400/415 V if that is the African system) |
| Ui | Rated insulation voltage | 660 V |
| fn | Frequency | 50 Hz |
| InA / Inc | Main / distribution bus current | Sample 4 000 A / 1 000 A (family window printed separately on the CCC) |
| Icw | Short-time withstand of the bus | Sample 80 kA main / 50 kA distribution |
| IP | Enclosure | IP30 indoor — not an outdoor figure |
| Form of separation | IEC 61439-2 internal separation | Not stated on the cover pages. Write Form 2b / 3b / 4b in the bid; do not assume it from the type code MNS. |
| Incoming device | ACB / MCCB rating and breaking | Must match transformer LV current and site Icc. Not a kVA line. |
Do not score an MNS bid with a transformer type-test or with a YB kiosk report. Conversely, do not skip the routine (factory) tests of the delivered columns: dielectric, protective-circuit continuity and function of every drawer. Two files: design type-test family, and the serial of the boards on the truck.
China LV-assembly standard GB 7251.12 vs IEC 61439-2
The 2015 file is a CCC safety type-test plus a CQC compulsory certificate. Read the dates and the sample ratings; do not treat an expired China CCC as a current African CoC.
| Subject | On the Yinma 2015 file | IEC counterpart |
|---|---|---|
| LV PSC assembly (the MNS board) | GB 7251.12-2013 | IEC 61439-2 |
| General rules for assemblies | GB 7251.1 (not printed on these three pages) | IEC 61439-1 |
| China compulsory certification | CCC / CNCA-C03-01:2014, CQC | Not an African import CoC — SONCAP / KEBS / SANS remain separate |
Safety type-test report 02401-150019314302-S, 53 pages, CNAS L0116 (Zhejiang Academy of Quality Inspection Science / Zhejiang Fangyuan). Applicant, manufacturer and production enterprise: Zhejiang Yinma Electric Co., Ltd., Yang’ao Village, Yanpen Subdistrict, Yueqing. Sample: one set of three columns, serials 201501022 / 201501023 / 201501024, received 12 March 2015, tests completed 16 April 2015. Conclusion printed: safety type test passed. Issued 25 April 2015. The CCC certificate No. 2015010301825855 was issued 1 December 2015 and printed valid until 1 December 2020. That expiry is on the paper: do not present this CCC as currently in force. Use it as design-family evidence; ask for the factory tests of the boards being shipped and for the destination-country CoC.



This pack is the LV-switchgear evidence for the MNS series discussed here. It does not replace S11-M, SCB18 or YB-12 reports, and those reports do not replace it. If the bid Icw, IP or incoming current sit outside the tested sample, ask which pages of the 53-page file still cover the offered column.
Five parameters that actually freeze an MNS design
Voltage and “MNS” on one line get you a catalogue photo. The board is frozen by incomer, Icw, drawer list, IP and cooling.
System and incomer
400/415 V, 50 Hz, 3P+N+PE. Incoming ACB from transformer LV current (e.g. 1 250 kVA at 0.4 kV ≈ 1 800 A — size the incomer, not the main bus copy-paste). Write 415 V if that is the site; 380 V is the Chinese test voltage.
Short-circuit Icw / Icc
Site prospective current at the LV bus. The tested sample is 80 kA main / 50 kA distribution. Do not write 100 kA because it appears on the CCC family line unless the offered bus is that design.
Functional units
Drawer schedule: motor feeders, MCCB feeders, ATS, capacitor, metering. Withdrawable vs fixed is a line, not a footnote. Form of separation (2b / 3b / 4b) belongs here — it is not on the three cover pages.
Room and cooling
Indoor IP30 on the file. Dust, coastal air, 45 °C: raise IP and state forced vs natural ventilation. The type-test used ten 65 W fans; copy that only if the room has equivalent airflow.
Documents
GB 7251.12 / IEC 61439-2 mapping + factory tests of the delivered serials + destination CoC. Do not file an expired China CCC as the only certificate, and do not write “IEC 60076 LV panel”.
Where an MNS board belongs — and where GGD or a kiosk LV cubicle is enough
Withdrawable MNS earns its freight when many feeders must be isolated live and the LV room is indoor. It is the wrong product for a rural pole, and it is not a substitute for the LV compartment of a YB kiosk unless the kiosk specification says so.
| Site | Why MNS | Specify in the protocol |
|---|---|---|
| Industrial LV room / PCC | Many motor and process feeders, live isolation | Icw, drawer list, Form, incomer ACB |
| Hospital / data room indoor | Maintain feeders without shutting the bus | IP, residual-current, generator incomer |
| Mine workshop indoor | Replaceable drawers, high Icw | Dust IP, Icw vs mine Icc |
| Simple factory with few feeders | Fixed GGD is usually enough | Do not pay for drawers the site will not use |
| Outdoor pad or pole | No indoor IP30 room | YB kiosk or outdoor-rated enclosure — not this MNS file |
kVA sizes the transformer. Icw, the incomer and the drawer list size the LV board. Five lines still suffice — they are not the five lines of S11-M, SCB18 or YB-12.
Four questions that are specific to the LV board, not the transformer
- Is 380 V the same as 415 V? 380 V is Ue on the 2015 Chinese sample. African 400/415 V systems must be written in the protocol. Insulation Ui 660 V on the file is usually enough for 415 V, but the incomer, CT and meter ratings still change.
Can we accept a transformer or YB type-test instead of GB 7251.12? No. Those files prove the transformer or the outdoor kiosk. The MNS file proves the indoor PSC assembly, bus Icw and IP30.
Does the CCC still cover shipments in 2026? The printed validity ended 1 December 2020. Treat the pack as historical design evidence. For a live order: factory tests of the serials + destination CoC (SONCAP / KEBS PVoC / SANS). Do not photocopy an expired CCC as a current certificate.
How do you verify a China LV-switchgear factory? (1) Type-test Icw, Ue, IP and withdrawable construction cover the bid. (2) The plant builds the assembly, not a traded empty shell around bought breakers with no assembly test. (3) Protocol states GB 7251.12 / IEC 61439-2, incomer, Icw, drawer list, IP, cooling, and Form of separation. (4) Temperature-rise conditions (fans or not) match the room.
Enquire with the board five, not the transformer five
Ue / incomer · Icw · drawer list · IP / cooling · Form of separation
Yinma Electric will return an MNS column sketch, GB 7251.12 / IEC 61439-2 mapping and the factory test list for African 400/415 V indoor rooms.