MNS Withdrawable LV Switchgear Selection
China LV Switchgear · GB 7251.12 and IEC 61439-2

Yinma Electric Co., Ltd. is a China manufacturer of transformers and low-voltage assemblies in Yueqing, Zhejiang. An MNS board is not a transformer and not a compact-substation kiosk: it is a withdrawable power switchgear assembly (PSC) under GB 7251.12 / IEC 61439-2. Engineer Xu Jianye wrote this guide from the 2015 CNAS safety type-test file — ratings, indoor IP, temperature-rise conditions, and how to specify for African 400/415 V rooms.

MNS
Product series
380V
Tested Ue
4000A
Main bus sample
IEC 61439
Assembly family

Do not specify an LV board as if it were a transformer or a YB kiosk

S11-M and SCB18 on this site are IEC 60076 apparatus. YB-12 is an IEC 62271-202 outdoor assembly. MNS is an indoor low-voltage PSC under IEC 61439-2. A kVA nameplate does not define this product.

    Assembly, not a winding. The type test is on the complete board: enclosure, main bus, distribution bus, withdrawable functional units and the incoming device. Two document families. The board follows GB 7251.12 / IEC 61439-2. Breakers, contactors and meters inside still have their own component certificates — those sheets do not replace the assembly type-test. Room interface. Incoming current, short-circuit Icw, form of separation, IP, indoor vs outdoor, and whether drawers or fixed feeders are required must be written before price comparison. If omitted, a Chinese indoor MNS is quoted at Ue 380 V, IP30, 1 000 m / 40 °C.

What “MNS” means on a Chinese LV RFQ

MNS is a withdrawable low-voltage complete switchgear layout used in GB 7251.12 《低压成套开关设备和控制设备 第2部分:成套电力开关和控制设备》.

On Yinma’s file the product name is 抽出式低压成套开关柜 (withdrawable LV complete switchgear) and the type is MNS. It is a PSC assembly: functional units withdraw on drawers, the bus is rear or top, the incomer is usually an ACB. It is not GGD (fixed panel), not GCS (another Chinese withdrawable family), and not the LV compartment of a YB kiosk — that compartment is a component of IEC 62271-202, not a substitute for an IEC 61439-2 board type-test.

What you are buyingGoverning standardWhat the type test provesWhat it does not replace
Oil or dry transformerGB 1094 / IEC 60076Tank or cast windings, lossesBusbar Icw, drawers, LV IP
YB compact substationGB/T 17467 / IEC 62271-202Outdoor HV–transformer–LV kioskA full indoor LV room board
MNS withdrawable LV boardGB 7251.12 / IEC 61439-2Indoor PSC assembly, bus, IPA transformer or kiosk report

African tenders still write “IEC 60439 LV panel”. IEC 60439 was withdrawn. The in-force counterpart of GB 7251.12-2013 is IEC 61439-2 (power switchgear and controlgear assemblies), with IEC 61439-1 as the general rules. If the bid only cites 60439, map it in the protocol; do not leave the edition blank.

What actually distinguishes an MNS board

Rated voltage is the easy line. The board fails in the field when Icw, drawer scheme, temperature-rise ventilation and IP are left as “standard MNS”.

01

Withdrawable units

Feeders and motor starters sit in drawers that isolate from the bus for maintenance. Draw count, module height and whether the ACB is withdrawable must appear on the SLD. A GGD-style fixed door is a different product — do not mix the two on one line item.

02

Main and distribution bus

Yinma’s tested sample: main bus InA 4 000 A, Icw 80 kA; distribution bus Inc 1 000 A, Icw 50 kA. The CCC family listing also prints a wider main-bus window (see the certificate caption). Quote the bus you will actually install, not the highest number on any page.

03

Indoor enclosure

The file is 户内型, IP30. That is a dry LV room, not an outdoor pad. Coastal or dusty African rooms often need IP42 / IP54 and a corrosion class — write them; IP30 will not appear by magic.

04

Temperature-rise set-up

The 2015 report notes that during the temperature-rise test ten 65 W fans were running. If the site has no forced ventilation, that test does not prove an unventilated column. State natural vs forced cooling in the protocol.

Quantities that belong on an MNS RFQ

These are assembly ratings. Transformer kVA only sizes the incomer; it does not define the board.

QuantityMeaningOn Yinma’s tested MNS sample
UeRated operational voltage380 V (write 400/415 V if that is the African system)
UiRated insulation voltage660 V
fnFrequency50 Hz
InA / IncMain / distribution bus currentSample 4 000 A / 1 000 A (family window printed separately on the CCC)
IcwShort-time withstand of the busSample 80 kA main / 50 kA distribution
IPEnclosureIP30 indoor — not an outdoor figure
Form of separationIEC 61439-2 internal separationNot stated on the cover pages. Write Form 2b / 3b / 4b in the bid; do not assume it from the type code MNS.
Incoming deviceACB / MCCB rating and breakingMust match transformer LV current and site Icc. Not a kVA line.

Do not score an MNS bid with a transformer type-test or with a YB kiosk report. Conversely, do not skip the routine (factory) tests of the delivered columns: dielectric, protective-circuit continuity and function of every drawer. Two files: design type-test family, and the serial of the boards on the truck.

China LV-assembly standard GB 7251.12 vs IEC 61439-2

The 2015 file is a CCC safety type-test plus a CQC compulsory certificate. Read the dates and the sample ratings; do not treat an expired China CCC as a current African CoC.

SubjectOn the Yinma 2015 fileIEC counterpart
LV PSC assembly (the MNS board)GB 7251.12-2013IEC 61439-2
General rules for assembliesGB 7251.1 (not printed on these three pages)IEC 61439-1
China compulsory certificationCCC / CNCA-C03-01:2014, CQCNot an African import CoC — SONCAP / KEBS / SANS remain separate

Safety type-test report 02401-150019314302-S, 53 pages, CNAS L0116 (Zhejiang Academy of Quality Inspection Science / Zhejiang Fangyuan). Applicant, manufacturer and production enterprise: Zhejiang Yinma Electric Co., Ltd., Yang’ao Village, Yanpen Subdistrict, Yueqing. Sample: one set of three columns, serials 201501022 / 201501023 / 201501024, received 12 March 2015, tests completed 16 April 2015. Conclusion printed: safety type test passed. Issued 25 April 2015. The CCC certificate No. 2015010301825855 was issued 1 December 2015 and printed valid until 1 December 2020. That expiry is on the paper: do not present this CCC as currently in force. Use it as design-family evidence; ask for the factory tests of the boards being shipped and for the destination-country CoC.

Yinma Electric MNS withdrawable LV switchgear CCC type-test report cover, CNAS L0116, report 02401-150019314302
CCC type-test report cover — 国家强制性产品认证试验报告, No. 02401-150019314302. Product: withdrawable LV complete switchgear, type MNS. New application A2015CCC0301-1975915. Testing body: Zhejiang Academy of Quality Inspection Science / Zhejiang Fangyuan (CNAS L0116). MA 2013110161Z. This cover is an LV assembly file, not a transformer file.
Page 1 of Yinma Electric MNS safety type-test report 02401-150019314302-S listing GB 7251.12-2013 ratings
Safety type-test page 1 — No. 02401-150019314302-S, 53 pages. GB 7251.12-2013. Ue 380 V, Ui 660 V, 50 Hz, indoor IP30. Sample main bus 4 000 A / Icw 80 kA; distribution bus 1 000 A / Icw 50 kA. Note on the form: ten 65 W fans on during temperature-rise; three-column set lifted as one. Conclusion: 安全型式试验合格.
CQC CCC certificate 2015010301825855 for Zhejiang Yinma Electric MNS withdrawable LV switchgear, valid 2015-12-01 to 2020-12-01
CCC certificate No. 2015010301825855, CQC, issued 1 December 2015, printed valid to 1 December 2020. Family listing: MNS main bus InA 6 300 A–4 000 A, Icw 100 kA; distribution Inc 1 000 A–400 A, Icw 50 kA; Ue 380 V, Ui 660 V; 50 Hz; IP30; GB 7251.12-2013. The type-test sample was 4 000 A / 80 kA — do not treat the wider CCC window as the tested sample. The printed validity has ended; destination CoC is a different document.

This pack is the LV-switchgear evidence for the MNS series discussed here. It does not replace S11-M, SCB18 or YB-12 reports, and those reports do not replace it. If the bid Icw, IP or incoming current sit outside the tested sample, ask which pages of the 53-page file still cover the offered column.

Five parameters that actually freeze an MNS design

Voltage and “MNS” on one line get you a catalogue photo. The board is frozen by incomer, Icw, drawer list, IP and cooling.

System and incomer

400/415 V, 50 Hz, 3P+N+PE. Incoming ACB from transformer LV current (e.g. 1 250 kVA at 0.4 kV ≈ 1 800 A — size the incomer, not the main bus copy-paste). Write 415 V if that is the site; 380 V is the Chinese test voltage.

Short-circuit Icw / Icc

Site prospective current at the LV bus. The tested sample is 80 kA main / 50 kA distribution. Do not write 100 kA because it appears on the CCC family line unless the offered bus is that design.

Functional units

Drawer schedule: motor feeders, MCCB feeders, ATS, capacitor, metering. Withdrawable vs fixed is a line, not a footnote. Form of separation (2b / 3b / 4b) belongs here — it is not on the three cover pages.

Room and cooling

Indoor IP30 on the file. Dust, coastal air, 45 °C: raise IP and state forced vs natural ventilation. The type-test used ten 65 W fans; copy that only if the room has equivalent airflow.

Documents

GB 7251.12 / IEC 61439-2 mapping + factory tests of the delivered serials + destination CoC. Do not file an expired China CCC as the only certificate, and do not write “IEC 60076 LV panel”.

Where an MNS board belongs — and where GGD or a kiosk LV cubicle is enough

Withdrawable MNS earns its freight when many feeders must be isolated live and the LV room is indoor. It is the wrong product for a rural pole, and it is not a substitute for the LV compartment of a YB kiosk unless the kiosk specification says so.

SiteWhy MNSSpecify in the protocol
Industrial LV room / PCCMany motor and process feeders, live isolationIcw, drawer list, Form, incomer ACB
Hospital / data room indoorMaintain feeders without shutting the busIP, residual-current, generator incomer
Mine workshop indoorReplaceable drawers, high IcwDust IP, Icw vs mine Icc
Simple factory with few feedersFixed GGD is usually enoughDo not pay for drawers the site will not use
Outdoor pad or poleNo indoor IP30 roomYB kiosk or outdoor-rated enclosure — not this MNS file

kVA sizes the transformer. Icw, the incomer and the drawer list size the LV board. Five lines still suffice — they are not the five lines of S11-M, SCB18 or YB-12.

— Xu Jianye, Yinma Electric design engineer

Four questions that are specific to the LV board, not the transformer

    Is 380 V the same as 415 V? 380 V is Ue on the 2015 Chinese sample. African 400/415 V systems must be written in the protocol. Insulation Ui 660 V on the file is usually enough for 415 V, but the incomer, CT and meter ratings still change.

    Can we accept a transformer or YB type-test instead of GB 7251.12? No. Those files prove the transformer or the outdoor kiosk. The MNS file proves the indoor PSC assembly, bus Icw and IP30.

    Does the CCC still cover shipments in 2026? The printed validity ended 1 December 2020. Treat the pack as historical design evidence. For a live order: factory tests of the serials + destination CoC (SONCAP / KEBS PVoC / SANS). Do not photocopy an expired CCC as a current certificate.

    How do you verify a China LV-switchgear factory? (1) Type-test Icw, Ue, IP and withdrawable construction cover the bid. (2) The plant builds the assembly, not a traded empty shell around bought breakers with no assembly test. (3) Protocol states GB 7251.12 / IEC 61439-2, incomer, Icw, drawer list, IP, cooling, and Form of separation. (4) Temperature-rise conditions (fans or not) match the room.

Author and manufacturer

Xu Jianye is a design engineer at Yinma Electric Co., Ltd., responsible for LV-assembly and transformer export protocols and GB 7251.12 / IEC 61439-2 mapping. Yinma Electric manufactures distribution transformers, compact substations and low-voltage switchgear in Yueqing, Zhejiang. The 2015 CCC file is issued to Zhejiang Yinma Electric Co., Ltd. at Yang’ao Village, Yanpen, Yueqing. Contract values follow the signed technical protocol. Related notes on this site (S11-M, SCB18, YB-12) cover the transformer or the outdoor kiosk, not the indoor MNS board.

Enquire with the board five, not the transformer five
Ue / incomer · Icw · drawer list · IP / cooling · Form of separation

Yinma Electric will return an MNS column sketch, GB 7251.12 / IEC 61439-2 mapping and the factory test list for African 400/415 V indoor rooms.

Further Reading

Yinma Electric YB-12 HV/LV prefabricated compact substation kiosk
Technical Guide

YB-12 Compact Substation Selection: China Package Substation GB/T 17467 vs IEC 62271-202

Engineer Xu Jianye maps YB□-12/0.4-1250 kiosk ratings, three compartments, and GB/T 17467 type tests to IEC 62271-202 — with Yinma Electric’s CNAS report for African 11 kV pad-mount sites.

Read Article →
Yinma Electric SCB18 cast-resin dry-type transformer
Technical Guide

SCB18 Dry-Type Transformer Selection: China Cast-Resin GB/T 10228 vs IEC 60076-11

Engineer Xu Jianye maps SCB18-NX1 ratings, AN cooling, Dyn11, and GB/T 1094.11 type tests to IEC 60076-11 — with Yinma Electric’s CNAS type-test report for indoor African 11 kV substations.

Read Article →
Yinma Electric S11-M hermetically sealed oil-immersed distribution transformer
Technical Guide

S11-M Sealed Oil Transformer Selection: China Transformer GB/T 6451 vs IEC 60076

Engineer Xu Jianye maps S11-M ratings, ONAN temperature rise, Dyn11, and GB 1094 type tests to IEC 60076 — with Yinma Electric’s CNAS type-test report for African 11 kV / 33 kV buyers.

Read Article →