After-Sales Service
Transformer after-sales support backed by factory-trained engineers in Nigeria, Kenya, and South Africa. We commit to responding to service requests within one business day, providing remote diagnosis within 48 hours, and dispatching field engineers for on-site power equipment maintenance service when required.
Warranty Policy
Our standard warranty protects against manufacturing defects in materials and workmanship. Extended coverage is available for utility and mining contracts requiring multi-year operational assurance.
Warranty Period
- Standard: 12 months from energization or 18 months from ex-factory delivery — whichever occurs first
- Extended warranty: up to 36 months available for utility grid and mining power supply contracts
- Spare parts: 12 months from shipment date when supplied separately under service agreement
- Warranty clock starts upon successful FAT and documented handover at destination port or site
Warranty Coverage
- Manufacturing defects in core, windings, insulation system, tank, and bushings
- Premature failure of tap changers, radiators, and factory-installed control accessories
- Performance deviation from agreed IEC 60076 test values confirmed at FAT
- Free replacement or repair of defective OEM components under warranty claim approval
- Remote technical support and troubleshooting guidance throughout the warranty period
Exclusions & Limitations
- Damage from improper installation, operation outside rated parameters, or unauthorized modification
- Normal wear items: gaskets, seals, silica gel, paint deterioration, and consumable lubricants
- Force majeure events: lightning strikes, floods, civil unrest, and grid-side fault damage
- Third-party component failures not supplied or approved by Transformer Africa
- Costs of crane hire, site access, and local labor unless covered under a separate service contract
Full legal terms on our warranty policy page.
Technical Support Channels
Three tiers of transformer after-sales support — from remote diagnosis to on-site power equipment maintenance service and operator training.
Remote Technical Support
Response within 1 business dayFactory engineers diagnose faults via email, phone, and video call — reviewing DGA oil analysis, thermal images, protection relay logs, and vibration data remotely.
- SCADA and protection relay data review
- Thermal imaging and partial discharge interpretation
- Tap changer and cooling system fault analysis
On-Site Field Service
Site visit within 5–10 business daysCertified field engineers dispatched to substations, mining sites, and industrial plants across Nigeria, Kenya, and South Africa for inspection, repair, and commissioning.
- Installation supervision and commissioning
- Bushing replacement and tap changer servicing
- Post-fault inspection and root cause reporting
Video Guidance & Training
Same-day for scheduled sessionsStep-by-step video walkthroughs for routine maintenance, oil sampling, bushing inspection, and protection setting verification — supplemented by live video calls with engineers.
- Operator maintenance training sessions
- Live video troubleshooting during outage windows
- Recorded guides for bushing, gasket, and silica gel procedures
OEM Spare Parts Supply
Genuine OEM spare parts manufactured to original specifications — ensuring compatibility, warranty validity, and long-term transformer reliability. Critical spares kits can be pre-positioned at Lagos, Mombasa, and Durban for contract customers.
OEM Replacement Parts
Factory-original components with full traceability and test certification.
- HV and LV bushings (porcelain and resin-impregnated)
- On-load tap changers (OLTC) and de-energized tap switches
- Radiator valves, fans, and oil pumps
- Pressure relief devices, Buchholz relays, and oil level gauges
- Winding temperature indicators (WTI) and oil temperature indicators (OTI)
- Control cabinets, AVR boards, and cooling controller modules
Consumables & Maintenance Kits
Routine service items for scheduled transformer maintenance programs.
- Tank gasket sets and flange seal kits
- Silica gel breather cartridges and oil filter elements
- Anti-condensation heater elements and thermostat switches
- Touch-up paint kits for tropical and coastal environments
- Bushing cleaning compounds and contact grease
- Annual maintenance tool kits with torque specifications
Daily Maintenance Guide
Recommended routine checks for oil-immersed and dry-type transformers — expand each item for detailed procedures.
Oil level and leak inspection (oil-immersed units)
Check conservator oil level against temperature-corrected mark weekly. Inspect tank welds, radiator flanges, and valve joints for seepage. Tighten flange bolts only to specified torque — over-tightening damages gaskets.
Silica gel breather and moisture control
Inspect breather silica gel color monthly — replace when predominantly pink (indicating saturation). In tropical climates, check every two weeks during rainy season. Ensure breather pipe is unobstructed and oil cup is filled.
Cooling system and fan operation
Verify radiator fans start at configured temperature setpoints. Clean radiator fins quarterly in dusty mining or industrial environments. Listen for bearing noise and check fan motor current against nameplate values.
Bushing and terminal connection check
Inspect bushings for cracks, oil staining, and corona marks during scheduled outages. Thermograph bolted connections annually. Clean porcelain surfaces and apply approved bushing compound per maintenance manual.
Dry-type transformer ventilation
Ensure ventilation grilles are unobstructed and room temperature stays below rated ambient. Vacuum dust from coil surfaces during annual outage. Check anti-condensation heaters are operational before rainy season.
Common Fault Troubleshooting
Initial diagnosis steps for frequent operational issues. Contact after-sales support if symptoms persist after these checks.
Abnormal noise or increased vibration
Possible causes: loose core clamping, fan imbalance, or through-fault mechanical stress. De-energize if vibration increased suddenly after a grid event. Contact after-sales support with audio recording and protection relay event log for remote assessment.
High winding or oil temperature alarm
Check cooling fan operation, radiator valve positions, and ambient temperature against rated limits. Verify load does not exceed nameplate kVA. If temperature rises under normal load, perform DGA oil analysis and contact engineering for thermal model review.
Buchholz relay or pressure relief device activation
Do not re-energize until investigated. Collect gas sample from Buchholz relay for laboratory analysis. Inspect for oil leaks, internal arcing evidence, and tap changer misalignment. Escalate immediately to factory after-sales team.
Low insulation resistance or failed megger test
Ensure winding temperature correction is applied to measured values. Check for moisture ingress via breather failure or damaged gasket. Dry out windings per IEC procedure if moisture is confirmed. Factory support available for PI and tan-delta interpretation.
Tap changer irregular operation or position error
Verify drive mechanism lubrication and motor supply voltage. Check position indicator matches relay setting. Do not force manual operation beyond stop limits. OLTC oil filter and contact inspection required per maintenance schedule — request OEM spare kit if contacts are pitted.
Protection relay tripping without obvious fault
Download event records and oscillography from relay before reset. Compare against nameplate CT ratios and protection settings. Check for inrush, sympathetic tripping, or external cable faults. Our engineers can review relay files remotely within 24 hours.
Service Process
Every after-sales case follows a structured five-step workflow — from initial report through resolution and follow-up confirmation.
Report Issue
Submit a service request with equipment serial number, fault description, and photos. WhatsApp and email channels available for urgent substation outages.
Engineer Response
Assigned service engineer acknowledges receipt within one business day and requests additional diagnostic data if needed.
Diagnosis
Remote analysis of test results, relay logs, and visual evidence. On-site inspection scheduled when remote diagnosis is inconclusive.
Resolution
Repair guidance, spare parts dispatch, or field engineer deployment. Warranty claims processed with root cause report and corrective action plan.
Follow-Up
Post-service confirmation call and written service report. Maintenance recommendations updated in customer file for future reference.
Submit a Service Request
Submit your after-sales service request with equipment details and fault description. Our engineering team will assign a service case number and respond within one business day.
- Include equipment serial number from the nameplate
- Attach photos or relay event logs via follow-up email
- Mark as urgent for active substation outages
Need Immediate Assistance?
Submit a service request below or contact your regional after-sales team directly for warranty claims, spare parts orders, and emergency substation support.
Review FAQ or customization services for related inquiries.