Technical data sheet · Updated 2026-11-06
400 kVA 20/15 kV Oil-Immersed Distribution Transformer (S11-M-400/20-15-0.4)
400 kVA · 20/15 kV / 0.4 kV · ONAN · Three-phase · IEC 60076
- Rated capacity
- 400 kVA
- Voltage ratio
- 20 / 0.4 kV
- No-load loss
- 590±15%
- Load loss
- 4970±15%
All 28 ratings
Overview
The S11-M-400/20-15-0.4 is a 400 kVA three-phase oil-immersed distribution transformer built to IEC 60076. It steps 20 kV down to 0.4 kV for MV/LV distribution networks, using ONAN cooling and a D,yn11 vector group, with 5%±10% short-circuit impedance.
No-load loss is 590±15% and load loss is 4970±15%. Tapping range is -5%, -2.5%, 0, +2.5%, +5%, and the unit is rated for ambient temperatures up to 40 °C. Every unit is routine-tested before shipment; type test reports and third-party CNAS certificates are released with the quotation.
Typical applications include rural grid extension, industrial plants, mining and quarrying, commercial estates and water treatment works in Nigeria, Kenya, South Africa, Ghana and Tanzania.
- Rural grid electrification
- Industrial plants
- Mining and quarrying
- Commercial buildings
- Water treatment
Key specifications
| Parameter | Unit | Value |
|---|---|---|
| Rated capacity | KVA | 400 |
| Rated voltage (HV) | kV | 20±2*2.5% |
| Rated voltage (LV) | kV | 0.4 |
| Vector group | — | D,yn11 |
| Cooling method | — | ONAN |
| No-load loss (P0) | W | 590±15% |
| Load loss (Pk) | W | 4970±15% |
| Short-circuit impedance (Uk) | % | 5%±10% |
Full technical data
1 · General data
| Parameter | Unit | Value |
|---|---|---|
| Model | — | S11-M-400/20-15-0.4 |
| Rated capacity | KVA | 400 |
| Rated voltage (HV) | kV | 20±2*2.5% |
| Rated voltage (LV) | kV | 0.4 |
| Rated current (HV) | A | 11.55 |
| Rated current (LV) | A | 577.4 |
| Number of phases (HV) | — | 3 |
| Number of phases (LV) | — | 3 |
| Frequency | HZ | 50/60 |
2 · Tapping & connection
| Parameter | Unit | Value |
|---|---|---|
| Tapping range | % | -5%, -2.5%, 0, +2.5%, +5% |
| Tap changer type | — | Off-circuit tap changer |
| Vector group | — | D,yn11 |
3 · Performance data
| Parameter | Unit | Value |
|---|---|---|
| No-load loss (P0) | W | 590±15% |
| Load loss (Pk) | W | 4970±15% |
| Short-circuit impedance (Uk) | % | 5%±10% |
| No-load current (I0) | % | 1.1 |
| Winding temperature rise | k | ≤65 |
| Top-oil temperature rise | k | ≤55 |
| Sound pressure level (Lp, 1 m) | dB | ≤56 |
| Maximum ambient temperature | ℃ | 40 |
4 · Insulation & construction
| Parameter | Unit | Value |
|---|---|---|
| Power-frequency withstand voltage (HV/LV) | KV | 50/5 |
| Lightning impulse withstand voltage (HV) | KV | 125 |
| Insulation class | — | A |
| Winding material | — | CU/CU |
| Core material | — | Grain-oriented silicon steel |
| HV / LV bushings | — | BJL-20/300/BF-1/630 |
| Cooling method | — | ONAN |
| Colour | — | Sea grey B05 |
Dimensions, weights and packing data are not published — they are confirmed with the quotation, because they vary with core grade, tap changer and accessory configuration.
Technical documents & quotation
- Type test report — temperature rise, short-circuit withstand, lightning impulse
- Factory test report with measured no-load and load losses
- Third-party CNAS certificates
- Special-environment design notes — altitude, high ambient, coastal corrosion
Document packs are released to qualified buyers with a project reference. Send the rating, voltage ratio and destination port and we will reply with a quotation within one working day.
Get Quick Quote →Frequently asked questions
What are the losses of the 400 kVA transformer?
No-load loss is 590±15% and load loss is 4970±15%. Every unit is routine-tested to IEC 60076 and the measured values are recorded in the factory test report.
What does S11-M-400 mean?
S means three-phase, 11 is the loss series and M is the hermetically sealed tank. 400 is the rated capacity in kVA and 20/0.4 kV is the voltage ratio.
Which vector group and cooling method are used?
D,yn11 vector group with ONAN cooling, tapping range -5%, -2.5%, 0, +2.5%, +5%.
Can you supply SONCAP, KEBS or SANS documentation?
Yes. We prepare the technical file your appointed agent needs — type test reports, routine test certificates, nameplate data and the packing list. Certificates of Conformity are issued per importer and per shipment.
Are dimensions and weights available?
Dimensions, weights and packing data are confirmed with the quotation, because they vary with core grade, tap changer and accessory configuration.