Technical data sheet · Updated 2026-11-06

250 kVA 20 kV Oil-Immersed Distribution Transformer (S11-M-250/20-0.4)

250 kVA · 20 kV / 0.4 kV · ONAN · Three-phase · IEC 60076

Rated capacity
250 kVA
Voltage ratio
20 / 0.4 kV
No-load loss
420±15%
Load loss
3720±15%

Overview

The S11-M-250/20-0.4 is a 250 kVA three-phase oil-immersed distribution transformer built to IEC 60076. It steps 20 kV down to 0.4 kV for MV/LV distribution networks, using ONAN cooling and a D,yn11 vector group, with 5%±10% short-circuit impedance.

No-load loss is 420±15% and load loss is 3720±15%. Tapping range is -5%, -2.5%, 0, +2.5%, +5%, and the unit is rated for ambient temperatures up to 40 °C. Every unit is routine-tested before shipment; type test reports and third-party CNAS certificates are released with the quotation.

Typical applications include rural grid extension, industrial plants, mining and quarrying, commercial estates and water treatment works in Nigeria, Kenya, South Africa, Ghana and Tanzania.

  • Rural grid electrification
  • Industrial plants
  • Mining and quarrying
  • Commercial buildings
  • Water treatment

Key specifications

Key technical specifications
ParameterUnitValue
Rated capacityKVA250
Rated voltage (HV)kV20±2*2.5%
Rated voltage (LV)kV0.4
Vector group—D,yn11
Cooling method—ONAN
No-load loss (P0)W420±15%
Load loss (Pk)W3720±15%
Short-circuit impedance (Uk)%5%±10%

Full technical data

1 · General data
ParameterUnitValue
Model—S11-M-250/20-0.4
Rated capacityKVA250
Rated voltage (HV)kV20±2*2.5%
Rated voltage (LV)kV0.4
Rated current (HV)A7.2
Rated current (LV)A360.8
Number of phases (HV)—3
Number of phases (LV)—3
FrequencyHZ50/60
2 · Tapping & connection
ParameterUnitValue
Tapping range%-5%, -2.5%, 0, +2.5%, +5%
Tap changer type—Off-circuit tap changer
Vector group—D,yn11
3 · Performance data
ParameterUnitValue
No-load loss (P0)W420±15%
Load loss (Pk)W3720±15%
Short-circuit impedance (Uk)%5%±10%
No-load current (I0)%1.2
Winding temperature risek≤65
Top-oil temperature risek≤55
Sound pressure level (Lp, 1 m)dB≤54
Maximum ambient temperature℃40
4 · Insulation & construction
ParameterUnitValue
Power-frequency withstand voltage (HV/LV)KV50/5
Lightning impulse withstand voltage (HV)KV125
Insulation class—A
Winding material—CU/CU
Core material—Grain-oriented silicon steel
HV / LV bushings—BJL-20/300/BF-1/300
Cooling method—ONAN
Colour—Sea grey B05

Dimensions, weights and packing data are not published — they are confirmed with the quotation, because they vary with core grade, tap changer and accessory configuration.

Technical documents & quotation

  • Type test report — temperature rise, short-circuit withstand, lightning impulse
  • Factory test report with measured no-load and load losses
  • Third-party CNAS certificates
  • Special-environment design notes — altitude, high ambient, coastal corrosion

Document packs are released to qualified buyers with a project reference. Send the rating, voltage ratio and destination port and we will reply with a quotation within one working day.

Get Quick Quote →

Frequently asked questions

What are the losses of the 250 kVA transformer?

No-load loss is 420±15% and load loss is 3720±15%. Every unit is routine-tested to IEC 60076 and the measured values are recorded in the factory test report.

What does S11-M-250 mean?

S means three-phase, 11 is the loss series and M is the hermetically sealed tank. 250 is the rated capacity in kVA and 20/0.4 kV is the voltage ratio.

Which vector group and cooling method are used?

D,yn11 vector group with ONAN cooling, tapping range -5%, -2.5%, 0, +2.5%, +5%.

Can you supply SONCAP, KEBS or SANS documentation?

Yes. We prepare the technical file your appointed agent needs — type test reports, routine test certificates, nameplate data and the packing list. Certificates of Conformity are issued per importer and per shipment.

Are dimensions and weights available?

Dimensions, weights and packing data are confirmed with the quotation, because they vary with core grade, tap changer and accessory configuration.